Ningbo Tianan (Group) Co.,Ltd.

Ningbo Tianan (Group) Co.,Ltd

Manufacturer from China
Verified Supplier
8 Years
Home / Products / Load Switch /

12KV Outdoor High Voltage Load Switch Circuit Breaker Combined Apparatus

Contact Now
Ningbo Tianan (Group) Co.,Ltd.
Visit Website
City:ningbo
Province/State:zhejiang
Country/Region:china
Contact Person:MsLian Huanhuan
Contact Now

12KV Outdoor High Voltage Load Switch Circuit Breaker Combined Apparatus

Ask Latest Price
Brand Name :Tianan Electric
Model Number :FT6-12
Certification :VDE CCC
Place of Origin :China
MOQ :10 unit
Price :Pending
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :1000 PCS/year
Delivery Time :35 work days
Packaging Details :Wooden Case
Rated Voltage :12 Kv
Altitude :up to 3,000m Above Sea Level
Rated Current :630 a
Warranty :2 Years
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

12KV Outdoor High Voltage Load Switch Circuit Breaker Combined Apparatus
NINGBO TIANAN (GROUP) CO., LTD.

General
FN12 Series AC HV Load Switch is a kind of three phase high voltage switch apparatus, suitable for
12kV rated voltage, 50Hz rated frequency alternative current, It is mainly used in downtown power distribution station and industrial electric equipment of three phase ring main unit electricity circle or terminal power supply, for breaking and closing short circuit current.

Technical parameter

No. Item unit Parameter
1 Rated Voltage kV 12
2 Max. Working Voltage kV 12
3 Rated Frequency Hz 50
4 Rated Current A 100
5 Rated Short-circuit Switch-off Current kA 50
6 1min Power Frequency Withstand voltage(value), to ground, interphase/isolation break kA 42/48
7 Lighting Impluse Resisting Voltage (peak) to ground, interphase/isolation break kV 75/85
8 Fuse Link Striking Output Energy Kg ≈5
Technical Parameter of load switch with fuse
No. Item Unit Parameter
1 Rated Voltage kV 12
2 Max. Working Voltage kV 12
3 Rated Frequency Hz 50
4 Rated Current A 630
5 Rated Power load switch-off current A 630
6 5% rated power load switch-off current A 31.5
7 Rated capacity switch-off current A 10
8 Rated inductance switch-off current A 40
9 Rated transfer current kA 1.3
10 Rated short-time withstand current kA 20
11 Rated peak withstand current kA 50
12 Mechanical endurance cycle 2000

12KV Outdoor High Voltage Load Switch Circuit Breaker Combined Apparatus