Outdoor Pole Mounted High Voltage Vacuum Circuit Breaker Three Phase

Ask Latest Price
Video Channel
Brand Name :Tianan Electric
Model Number :ZW20A-12
Place of Origin :Ningbo,China
MOQ :5sets
Price :Pending
Payment Terms :T/T, L/C, D/A, D/P
Supply Ability :10000 sets per year
Delivery Time :45 days
Packaging Details :International Standard package
Rated Voltage :10kv 11kv 12kv
Rated Current :630A 1250A
Mechanical Life :10000 times
Altitude :≤1000m
Service condition :Outdoor
Rated Frequency :50Hz
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description
High Voltage Vacuum Circuit Breaker , Outdoor Pole-mounted Vacuum Breaker
General
ZW20A-12 Outdoor Pole-mounted Vacuum Circuit Breaker is a kind of outdoor distribution equipment, three-phase, AC50Hz, with rated voltage of 12kV. It is mainly used in power distribution network to break, open and close load current, overload current and short-circuit current. It is also used in substation, industrial and mining enterprises, urban and rural power grid for control and protection. And it is more suitable for frequency operation and the urban distribution automation network.

Model meaning:
Z W 20 A - 12 / T - 0 0
Z: vacuum circuit breaker
W: Outdoors
20A: Design Number
12: Rated voltage (KV)
T: spring operating mechanism
0: Rated current (A)
0: Rated short-circuit breaking current (kA)

Environmental Conditions

1. Altitude: ≤1000m; if applied in special conditions, it is designed to 2000m to 4000m to meet the requirements of different altitudes.
2. Ambient temperature: -45℃~+40℃;
3. Wind speed≤35m/s;
4. It is placed in the places without violent vibration

Technical Parameters

No. Item Unit Value
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current A 630
4 Rated short-circuit breaking current kA 20
5 Rated peak withstand current (peak) kA 50
6 Rated short-time withstand current/endurance kA/s 20/4
7 Rated short-circuit making current (peak) kA 50
8 Rated operating sequence O-0.3s-CO-180s-CO
9 Mechanical endurance Time 10000
10 Rated short circuit breaking current breaking times Time 30
11 Rated cable-charging breaking current A 25
12 Power frequency withstand voltage(1min): Dry test (wet) phase-to-phase, to earth/fracture(wet test) kV 42(34)/48(36)
13 Lightning impulse withstand voltage(peak) phase-to-phase, to earth/fracture kV 75/85
14 1min power frequency withstand voltage of secondary circuit kV 2